冷水機低壓報警六大原因及解決辦法

發布時間:2022-06-28 14:39:37 閱讀量:

冷水機(ji)低壓報警怎么辦?一、冷水機(ji)低壓故障是(shi)由于吸(xi)入壓(ya)力過低。壓(ya)縮機(ji)正(zheng)常(chang)吸(xi)氣壓(ya)力為0.4~0.6MPa。當吸(xi)入壓(ya)力低于0.2MPa時(shi),低壓(ya)保護繼電器動(dong)作(zuo)。過低,回風量不足,量達不到要求,造成不必要的功率損耗。所以,水冷冷水機廠在這里說說低壓報警的六大可能原因:
      
 

  1、檢查冷(leng)(leng)卻水(shui)(shui)(shui)溫(wen)(wen)度(du)是否過低(di)(di)。當(dang)外界溫(wen)(wen)度(du)過低(di)(di)時,打開冷(leng)(leng)卻水(shui)(shui)(shui)并(bing)在低(di)(di)溫(wen)(wen)下運行(xing);或油溫(wen)(wen)度(du)過低(di)(di),冰(bing)箱不能完全分離,造成(cheng)低(di)(di)壓故(gu)障。如果冷(leng)(leng)卻水(shui)(shui)(shui)溫(wen)(wen)度(du)過低(di)(di),請關閉或節流冷(leng)(leng)卻水(shui)(shui)(shui)以降低(di)(di)水(shui)(shui)(shui)溫(wen)(wen)。如果冷(leng)(leng)凍(dong)油溫(wen)(wen)度(du)過低(di)(di),可(ke)以延長冷(leng)(leng)水(shui)(shui)(shui)機的預熱時間,恢復正常冷(leng)(leng)凍(dong)油溫(wen)(wen)度(du)即可(ke)解(jie)決(jue)。

  2、檢查蒸(zheng)發(fa)器是(shi)否堵(du)塞。蒸(zheng)發(fa)器堵(du)塞造成熱(re)交換不良,無法蒸(zheng)發(fa)。因此(ci),在日常維護保養(yang)時,應定期對冷水機進(jin)行反沖洗。

  3、檢查制(zhi)冷劑(ji)是否不足或泄(xie)漏。

  4、檢查低(di)壓(ya)保護繼(ji)電器(qi)是否損壞(huai)。低(di)壓(ya)保護繼(ji)電器(qi)短路、接觸(chu)不(bu)良或受潮損壞(huai),造成通訊故障和誤報警。

  5、檢(jian)查(cha)冷(leng)(leng)水機(ji)的(de)膨(peng)脹(zhang)閥。如(ru)果制冷(leng)(leng)劑充足,膨(peng)脹(zhang)閥過小或(huo)堵塞(sai),也會造成螺桿式(shi)冷(leng)(leng)水機(ji)低壓故障。這個問題多(duo)是因為組低溫運(yun)行或(huo)者(zhe)制冷(leng)(leng)機(ji)組長(chang)時(shi)間沒有運(yun)行而(er)造成的(de),冷(leng)(leng)水機(ji)只需要運(yun)行一(yi)段時(shi)間就(jiu)可(ke)以恢復正(zheng)常。

  6、檢查冷水機系統是否有空氣或缺水。當冷媒機組系統有空氣或缺水時,會造成冷媒水流量不足、吸熱效果差、冷媒效果差、過冷、蒸汽過飽和等現象。會產生濕壓縮,導致機組進出水壓差減小,溫差變大,吸入溫度低,吸入口結霜。解決辦法是在管道高度處安裝排氣閥進行排氣;管道過濾器堵塞或選材太細,透水性受限。應選擇過濾器并定期清潔過濾器。水泵流量小,與系統不匹配。應選擇冷水機低壓故障,原因是壓縮機吸入壓力過低。壓縮機正常吸氣壓力為0.4~0.6MPa。當吸入壓力低于0.2MPa時,低壓保護繼電器動作。如果氣壓過低,回風量不足,達不到要求,就會產生不必要的功率損耗。